GV4PE Therm/Mag 115A 50kA Elink
£648.95 Incl. VAT
GV4PE THERM/MAG 115A 50KA ELINK · · · TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. · · It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. · · Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. · · Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. · · It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX).
Out of stock
Description
Technical Specifications Technical Specifications Motor protection circuit-breaker Width 81.00 mm Rated operation power at AC-3, 400 V 55.00 kW Number of poles 3.00 Rated permanent current Iu 115.00 A Height 155.00 mm Depth 116.00 mm Rated operation power at AC-3, 230 V 30.00 kW Rated short-circuit breaking capacity Icu at 400 V, AC 50.00 kA Rated operating voltage 0.00 – 690.00 V Overload release current setting 65.00 – 115.00 A Adjustment range undelayed short-circuit release 1955.00 – 1955.00 A With thermal overload protection Yes Phase failure sensitive Yes With integrated auxiliary switch No With integrated under voltage release No · Manual: https://asset.eezybridge.com/ad7e7626-8f4a-4edb-b78d-9ca040e321dd/2192425






