Eaton Bussmann 100M160A BS88 Industrial Offset Bolted Tag Fuse Link
Industrial offset bolted tags fuse links are specifically designed for the protection of general motor applications. · · · BS reference: A4 · · 1: 1: 6 selective coordination ratio between “minor” and “major” fuse · · gG characteristics for cable protection · · Power loss values within the limits of IEC 60269 · · Compatible with Red Spot fuse holder 100A RS100 · · Pre-arching: 72,500 · · Total at 415V: 190,000 · · Watts loss: 5
Description
Technical Specifications Technical Specifications HRC fuse Utilization category gM (motor protection) Colour code None Type of fuse status indicator None Fuse system according to IEC 60269 Fuse system E Mounting holes M8 Fuse construction type according to IEC 60269 A4 Current type AC Breaking capacity 80 kA Centre-to-centre distance of connections 93.5 mm Rated current 160 A Rated voltage AC 415 V Power loss at rated current 5 W · Technical Data Sheet – Click to Download